Immersion Cooling Liquid

Single phase Immersion Cooling Liquid, P ICE series

Immersion cooling with the best cooling effect among cooling solutions at present. It directly immerses heating devices such as servers, BMS and CPUs in non-conductive liquid, and directly transfer the heat energy generated by the heating element to the fluid with no other cooling solutions, such as heat-conducting copper pipes, fans, heat sinks, etc.. And the liquid whose temperature rises will flow back through the circulating cooling method to continue to absorb heat energy. It has been certified by major international companies to achieve the best cooling effect.

P ICE series advantages:

  1. The only immersion cooling product on the market that is produced in Taiwan and has been fully validated for mass production
  2. Adjustable to meet customer needs or customize suitable products
  3. The Taiwan laboratory can be used by customers to verify experiments and provide experimental data.
  4. Fast production, quality assurance, permanent after-sales service
  5. Biodegradable, no environmental hazards
石蠟

Application

  • Servers, Battery management system, energy storage system cooling
  • Electric vehicle, electric vehicle cooling
  • Mining machine, gaming computer cooling

Features and Benefits

  • Kinematic viscosity: 5~65 cSt@20℃
  • Excellent heat conduction and insulation
  • Well low temperature operation
  • Biodegradable and non-hazardous to the environment
Item Unit PICE-5 PICE-10 PICE-15 Test method
Color APHA 50 30 50 ASTM-D1209
Acid Value mg KOH/g 0.01 0.01 0.01 ASTM-D974
Water Content ppm 50 50 50 ASTM-D1533
Kinematic Viscosity cSt@20°C 5.2 10.1 14.8 ASTM-D445
Viscosity Index   177 122 126 ASTM-D2270
Density g/mL@20°C 0.861 0.926 0.925 ASTM-D4052
Coefficient of Expansion 1/°C@20°C 0.00087 0.00084 0.00081 ASTM-D1903
Flash point C.O.C °C 160 180 205 ASTM-D92
Pour point °C < -60 < -60 < -60 ASTM-D97
Global Warming Potential GWP < 1 < 1 < 1 -
Ozone Depleting Potential ODP 0 0 0 -
Biodegradability % > 60 > 60 > 60 OECD 301F
Breakdown Voltage KV@RT > 70 > 70 > 70 IEC 60156
Volume Resistivity GΩ*m@90°C 5.2 3.8 3.9 IEC 60247